AVK FIRE HYDRANT, SA, PN16

SA Hydrant, Screw-Down Type, AS/NZS 4087 B5

AVK Wingfield Plant

Contact

AVK Australia Civil

559A Grand Junction Road Wingfield SA 5013 Sales and Technical enquiry

AVK under ground hydrant isolation valve for fire protection services, water and neutral liquid applications

fire
fire
Variant 29/010-001
Connection: Flanged
Material: Ductile Iron
DN: DN80
PN: PN16
Closing direction: Clockwise Close

Features

  • Ductile Iron body for high strength and impact resistance
  • EPDM encapsulated plug for longlife and sealing reliability
  • O-Ring seals replaceable under pressure
  • Thermally bonded polymeric coating for long life protection to AS/NZS 4158
  • For fire protection services, water and neutral liquid applications
  • Valve designed for use up to 70oC
  • Where applicable; for AS/NZS 4020 compliance, max temp = 40oC
  • Insulation essential for installations subject to temperatures of 0oC and lower

           Note: Always observe pipe material recommended operating temperatures

Downloads

Datasheet
Installation, Operation & Maintenance

Reference nos. and dimensions:

Scroll for more info
AVK ref. no. DN
mm
L
mm
L1
mm
H
mm
H1
mm
Theoretical
weight/kg
29-010-8-4157302 80 185 88 392 250 15
Enquiry
Scroll for more info

Components

1. Body Ductile iron GJS-500-7
2. Stopper EPDM rubber
3. Stopper body Ductile iron GJS-500-7
4. Nut Brass, DZR CZ132
5. Stem Stainless steel 1.4057 (431)
6. Collar Brass, DZR
7. O-ring NBR rubber
8. O-ring NBR rubber
9. O-ring NBR rubber
10. Bonnet Ductile iron GJS-500-7
11. Gland flange Ductile iron GJS-500-7
12. Gland flange bolt Stainless steel A4-70
13. Thrust collar Brass, DZR CW602N
14. Bushing PA
15. Wiper ring NBR rubber
16. Bolt Stainless steel A4-70
17. Stem Cap Ductile iron GJS-500-7
18. Insert Plastic
19. Bolt Stainless steel A4-70

Standards

  • Flange drilling to AS/NZS 4087 B5
  • AS/NZS 4020 compliant
0 Files In the package