AVK FIRE HYDRANT, NT, PN16

Compact model with loose stopper for use in Northern Territory

AVK Wingfield Plant

Contact

AVK Australia Civil

559A Grand Junction Road Wingfield SA 5013 Sales and Technical enquiry

AVK under ground hydrant for fire protection services, water and neutral liquid applications

The Series 29/288 is a squat fire hydrant suitable for use with water and neutral liquids, to a maximum temperature of 70°C. .

 

Variant 29/288-003
Connection: Flanged
Material: Ductile Iron
DN: DN80
PN: PN16
Closing direction: Clockwise Close

Features

  • For fire protection services, water and neutral liquid applications
  • Valve designed for use up to 70 °C
  • Where applicable; for AS 4020 compliance, max temp = 40° C
  • Insulation essential for installations subject to temperatures of 0° C

 

Note: Always observe pipe material recommended operating temperatures

Downloads

Datasheet
Installation, Operation & Maintenance

Reference nos. and dimensions:

Scroll for more info
AVK ref. no. DN
mm
H
mm
L
mm
L1
mm
L2
mm
29-288-8-2285102 80 293 200 125 286.5
Enquiry
Scroll for more info

Components

1. Body Ductile iron GJS-500-7
2. O-ring NBR rubber
3. Outlet Stainless steel 316
4. Screw Stainless steel A4
5. Dust Cap PE
6. O-ring NBR rubber
7. O-ring NBR rubber
8. Gland flange Ductile iron GJS-500-7
9. Stem Cap Cast iron GJL-250 (GG-25)
10. Screw Steel gr. 8.8, hot dip galvanized
11. White Insert PE
12. Stopper EPDM rubber
13. Bonnet Ductile iron GJS-500-7
14. Nut Brass, DZR CZ132
15. Stem Stainless steel 1.4057 (431)
16. Thrust collar Brass, DZR CZ132
17. Screw Steel gr. 8.8, hot dip galvanized
18. O-ring NBR rubber
19. Gland flange bolt Steel gr. 8.8, hot dip galvanized
20. Bushing PA 6.6
21. O-ring NBR rubber
22. Wiper ring NBR rubber

Test/Approvals

  • Hydraulic test to BS750:

    -Seat: 1.1 x PN

    -Body: 1.5 x PN

Standards

  • Face to face: BS750
  • Universally drilled to AS 2129 Table D, DN80/DN90
  •  Coating to AS/NZS 4158
  • AS 4020 compliance
0 Files In the package