AVK FIRE HYDRANT, NZ, PN16

NZS 4522 - Tall model for use in New Zealand

AVK Wingfield Plant

Contact

AVK Australia Civil

559A Grand Junction Road Wingfield SA 5013 Sales and Technical enquiry

AVK under ground hydrant for fire protection services, water and neutral liquid applications

AVK Hydrant according to NZS 4522:2010 - for use in New Zealand. Screw-down type with 2-1/2" thread outlet and DN80 inlet.

Inlet flange to AS/NZS 4087.  

fire
fire
Variant 29/589-001
Connection: Flanged
Material: Ductile Iron
DN: DN80
PN: PN16
Closing direction: Clockwise Close

Features

  • For fire protection services, water and neutral liquid applications
  • Valve designed for use up to 70oC
  • Coating to AS/NZS 4158
  • Where applicable; for AS 4020 compliance, max temp = 40oC
  • Insulation essential for installations subject to temperatures of 0oC and lower

           Note: Always observe pipe material recommended operating temperatures

Downloads

Datasheet
Installation, Operation & Maintenance
Certificate(s)

Reference nos. and dimensions:

Scroll for more info
AVK ref. no. L
mm
H
mm
L1
mm
Theoretical
weight/kg
DN
mm
29-589-3-2185102 125 394 220 20 80
2D/3D drawings
Enquiry
Scroll for more info

Components

1. Body Ductile iron GJS-500-7
2. O-ring NBR rubber
3. Outlet Stainless steel 316
4. Outlet bolt Stainless steel A4
5. Dust Cap PE
6. O-ring NBR rubber
7. O-ring NBR rubber
8. Gland flange Ductile iron GJS-500-7
9. Stem Cap Ductile iron GJS-500-7
10. Screw Stainless steel A4
11. White Insert PE
12. Stopper EPDM rubber
13. Bonnet Ductile iron GJS-500-7
14. Fixed nut EPDM rubber
15. Bonnet bolt Stainless steel A4
16. Stem Stainless steel 1.4057 (431)
17. Thrust collar Brass, DZR CZ132
18. O-ring NBR rubber
19. Gland flange bolt Stainless steel A4
20. Bushing PA 6.6
21. O-ring NBR rubber
22. Wiper ring NBR rubber

Test/Approvals

  • Hydraulic test according to NZS 4522:2010:

                -Seat: 2,000 kPa (ASTP)

                -Body: 2,000 kPa (ASTP) 

Standards

  • Designed to: NZS 4522
  • Flange drilling to AS/NZS 4087 B5
  • AS/NZS 4020 compliance
0 Files In the package